Please use this identifier to cite or link to this item: https://repositori.uma.ac.id/handle/123456789/18365
Full metadata record
DC FieldValueLanguage
dc.contributor.authorDaut, I-
dc.contributor.authorMaizana, Dina-
dc.contributor.authorZakaria, S-
dc.contributor.authorUthman, S-
dc.contributor.authorTaib, S-
dc.date.accessioned2022-11-15T02:36:39Z-
dc.date.available2022-11-15T02:36:39Z-
dc.date.issued2006-
dc.identifier.issnISSN 1546-9239-
dc.identifier.urihttps://repositori.uma.ac.id/handle/123456789/18365-
dc.description3 Pagesen_US
dc.description.abstractThis paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60 was 10%, 12% and 15% better than the core with T-joint 45, T-joint 23 and T-joint 90 respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in caus ing the differences in performance.en_US
dc.language.isoenen_US
dc.publisherScience Publicationsen_US
dc.relation.ispartofseriesAmerican Journal of Applied Sciences;3 (9): 1990-1192, 2006-
dc.subjecttransformer coreen_US
dc.subjectflux distributionen_US
dc.subjectrotational fluxen_US
dc.subject3rd harmonic fluxen_US
dc.subjectpower lossen_US
dc.subjectbuilding factoren_US
dc.titleComparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T Joint Geometryen_US
dc.typeArticleen_US
Appears in Collections:Published Articles



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.