Please use this identifier to cite or link to this item: https://repositori.uma.ac.id/handle/123456789/18379
Full metadata record
DC FieldValueLanguage
dc.contributor.authorMaizana, Dina-
dc.date.accessioned2022-11-16T07:19:12Z-
dc.date.available2022-11-16T07:19:12Z-
dc.date.issued2009-09-
dc.identifier.isbnISBN:978-1-61567-750-4-
dc.identifier.urihttps://repositori.uma.ac.id/handle/123456789/18379-
dc.description16 Pagesen_US
dc.description.abstractThis paper describes the result of measurement of in- plane flux distribution on 100KVA 3phase distribution transformer assembled with 45 T-joint and mitred lap comer joint with stagger yoke and limb with overlap length of 10mm. The measurement involves the fundamental and third harmonic of the easy and hard direction of flux density at each location measurement. The flux distributions have been measured using no load test by arrays of search coil in M5 (CGO) grades material of transformer core laminations. The localised flux density at the outer 45 T-joint is 0.218T and rises to be 0.228T at the inner edges of 45 T-joint when the transformer core energized 1.5 T 50Hz. Harmonic occurs mostly in the T-joint where local regions are saturated and the flux deviates from the rolling direction. A small amount of flux deviation from the rolling direction occurs at the overlap, but no rotational flux is present in the joint. This paper describes the result of measurement of in plane flux distribution on 100kKVA 3phase distribution transformer assembled with 45 T-joint and mitred lap corer joint with stagger yoke and limb with overlap length of 10mm. The measurement involves the fundamental and ‘third harmonic of the easy and hard direction of flux density at each location measurement. The flux distributions have been measured using AO load test by arrays of Search coil In MS (CGO) grades material of transformer core laminations. The localised flux density at the outer 45 T-joint is 0.218T and rises to be 0.228T at the Inner edges of 45 T-joint when the transformer core energized 1.5 T S50Hz. Harmonic occurs mostly in the T-joint where local regions are saturated and the flux deviates from the rolling direction. A small amount of flux deviation from ‘the rolling direction occurs at the overlap, but no rotational flux is present in the joint.en_US
dc.language.isoenen_US
dc.publisherIASTED European Conference on Power and Energy Systemen_US
dc.relation.ispartofseriesEuroPES 2009;9th-
dc.subjecttransformer coreen_US
dc.subjectin plane flux distributionen_US
dc.subjectsearch coilen_US
dc.subjectgrain orienteden_US
dc.subjectsilicon ironen_US
dc.subjecttransformer coreen_US
dc.subjectnormal flux distributionen_US
dc.subjectfundamental fluxen_US
dc.titleIn-plane Flux Distribution in 45 T-joint of 3Phase Transformer Core with Staggered Yoke and Limb 10mmen_US
dc.title.alternativeNormal Flux Distribution in 45 T-joint of Three Phase Transformer Core with Staggered Yoke and Limb 10mmen_US
dc.typeArticleen_US
Appears in Collections:Published Articles



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.