Please use this identifier to cite or link to this item: https://repositori.uma.ac.id/handle/123456789/18408
Full metadata record
DC FieldValueLanguage
dc.contributor.authorDaut, I-
dc.contributor.authorMaizana, Dina-
dc.contributor.authorRosli, Izzat-
dc.contributor.authorIsa, Z Mat-
dc.contributor.authorZakaria, S-
dc.contributor.authorTaib, S-
dc.date.accessioned2022-11-17T06:04:42Z-
dc.date.available2022-11-17T06:04:42Z-
dc.date.issued2009-08-
dc.identifier.urihttps://repositori.uma.ac.id/handle/123456789/18408-
dc.description22 Pagesen_US
dc.description.abstractThis paper describes the result of simulation of flux distribution on 100kVA 3phase distribution transformer assembled with 23 T joint and mitred lap corner joint with stagger yoke and limb for one lamination. The simulation involves the variation of flux. The flux distribution have been simulated using 2DFEM by Quick field Software built from M5 (CGO) grades material of transformer core laminations. The flux density is 1.78 T maximum at the center limb of transformer core and the loss calculation is 1.274 W/kg. This paper describes the result of measurement of localized loss distribution on 100KVA 3phase distribution transformer assembled with 23 Tjoint and mired lap corner joint with staggered yoke. The measurement involves the variation of temperature rise. The localized loss have been measured using no load test by arrays of thermistor on the surface of MN5 (CGO) grades material of material of transformer core laminations. The localised loss at the outer 23 T joint is 1.05 W/kg and rises to be 1.26 W/kg at the inner 23 T-joint when the transformer core energized 1.5 T 50Hz. The several harmful effects can occur because the flux flows out of the rolling direction.en_US
dc.language.isoenen_US
dc.publisherInternational Conference on QiR (Quality in Research)en_US
dc.relation.ispartofseriesQiR;The 11th-
dc.subjectgrain oriented silicon ironen_US
dc.subjecttransformer coreen_US
dc.subject2dfemen_US
dc.subjectpower loss calculationen_US
dc.subjecttemperature riseen_US
dc.titleSimulation of Flux Distribution and Loss Calculation at Three-Phase Three Limbs of Transformer Core with 23 T-Jointen_US
dc.title.alternativeThe Localized Loss on 100kVA 3-Phase Distribution Transformer assembled with 23 T-jointen_US
dc.title.alternativeNormal Flux Distribution in 23 T-joint of Three Phase Transformer Core with Staggered Yoke 10mmen_US
dc.title.alternativeIn-plane Flux Distribution in 23 T-joint of 3Phase Transformer Core with Staggered Yoke 10mmen_US
dc.typeArticleen_US
Appears in Collections:Published Articles

Files in This Item:
File Description SizeFormat 
2.7.Prosiding Internasional ISSNISBN 114-1284 Berjudul The 11th International Conference on QIR.pdfProsiding dan Link2.75 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.