Title: Comparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T Joint Geometry
Authors: Daut, I
Maizana, Dina
Zakaria, S
Uthman, S
Taib, S
Keywords: transformer core;flux distribution;rotational flux;3rd harmonic flux;power loss;building factor
Issue Date: 2006
Publisher: Science Publications
Series/Report no.: American Journal of Applied Sciences;3 (9): 1990-1192, 2006
Abstract: This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60 was 10%, 12% and 15% better than the core with T-joint 45, T-joint 23 and T-joint 90 respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in caus ing the differences in performance.