Title: Measurement of Flux Distribution on 100kVA 3Phase Distribution Transformer Assembled With 45 T-Joint and Mitred Lap Corner Joint with Stagger Yoke by Using Search Coil
Authors: Daut, I
Maizana, Dina
Taib, S
Keywords: flux distribution;transformer core;search coil
Issue Date: Apr-2008
Publisher: IASTED International Conference Power and Energy Systems (AsiaPES 2008)
Series/Report no.: AsiaPES 2008;Proceedings of the Fourth
Abstract: This paper describes the result of measurement of flux distribution on 100KVA 3phase distribution transformer assembled with 45 T-joint and mitred lap CORNER joint with stagger yoke. The measurement involves the variation of flux The flux distributions have been measured using no load test by arrays of search coil in M5 (CGO) grades material of transformer core laminations. The localised flux density at the outer 45 T-joint is 90 mT and rises to be 148 mT at the inner 45 T-joint and the localised flux density at the outer corner-joint is 103 mT and rises to be 198 mT at the inner comer-joint when the transformer core energized 1 T 50H2 A small amount of flux deviation from the rolling direction occurs at the overlap.
Description: 10 Pages
URI: https://repositori.uma.ac.id/handle/123456789/18378
ISSN: ISBN CD:978-0-88986-732-1